Another project where our solution proved to be the best in terms of high energy efficiency, very low noise levels and, most importantly, compactness.
- 21,000 m³/h in an area of 4 m² (unitlength does not exceed 2.36 m),
- Rotary heat recovery system with 81% efficiency,
- Total motor power 9.5 kW (with free pressure of 700 Pa),
- Fans with EC motors, groups of fourunits operating in parallel,
- Twin heatexchangers (water — cooling / water — heating),
- Low noiselevels, 47.9 dB,
- Combination of G4 + F7 filters.