OPT-type clean air operating theatre ceiling.
Creates a turbulent, directional airflow. Best suited for hybrid and angiographic operating theatres, as well as CT and MRI diagnostic rooms.
For use in:
- Room groups 3, 4 and 5, according to GOST R 52539-2006
- Room classes A and B, according to SP 2.1.3678-20
- Room classes A and B, according toSP 158.13330.2014
- Class 6–7 cleanrooms (ISO 14664)
- Room classes A and B, room groups 3 and 5, according to the requirements of GOST R 71542-2024
Features:
- High-efficiency HEPA H13-H14 air filters, fully compliant with GOST R EN 1822-1-2010, with low pressure drop – included as standard;
- Fittings required for seal testing and measuring pressure drop across the filter are integrated into the housing;
- No special tools are required to replace the filter elements;
- Preparation for the DEHS test and pressure drop measurement tubes — standard equipment;
- Vacuum packaging and automatic scan test according to GOST R EN 1822-2014 during the manufacture of each filter.
| Model | OPT 5 | OPT 11 | |
|---|---|---|---|
| Air flow | M3/h | 600 | 1200 |
| Casing dimension | mm | 1080 x 410 x 720/830 | 2160 x 410 x 720/830 |
| Weight | kg | 55 | 110 |